APC UPS更换电池指示灯并报告“更换电池”

我们有一个APC智能UPS 1500.“更换电池”指示灯亮起,并报告:

Emergency! Batteries have failed on UPS xxxx. Change them NOW 

不过,从这篇文章中,

http://sturgeon.apcc.com/kbasewb2.nsf/for+external/f39c4312fcaf7b948525679a005ebb78?OpenDocument

似乎不太清楚UPS电池是否需要更换。 奇怪的是,根据UPS的信息,运行在27.7V的42.9%负载下的11分钟运行时间并不是那么糟糕。

任何关于下一步尝试的想法? 我们是一个非营利组织,金钱一个对象。 更换一年左右的电池将是一个耻辱。

 # apcaccess status APC : 001,041,1017 DATE : Thu Mar 29 13:01:41 EDT 2012 HOSTNAME : oreilly2 VERSION : 3.14.6 (16 May 2009) debian UPSNAME : xxxx CABLE : Custom Cable Smart MODEL : Smart-UPS 1500 UPSMODE : Stand Alone STARTTIME: Thu Mar 29 12:57:30 EDT 2012 STATUS : ONLINE LINEV : 112.3 Volts LOADPCT : 42.9 Percent Load Capacity BCHARGE : 100.0 Percent TIMELEFT : 11.0 Minutes MBATTCHG : 5 Percent MINTIMEL : 3 Minutes MAXTIME : 0 Seconds OUTPUTV : 112.3 Volts SENSE : High DWAKE : -01 Seconds DSHUTD : 090 Seconds LOTRANS : 106.0 Volts HITRANS : 127.0 Volts RETPCT : 000.0 Percent ITEMP : 23.8 C Internal ALARMDEL : Always BATTV : 27.7 Volts LINEFREQ : 60.0 Hz LASTXFER : No transfers since turnon NUMXFERS : 0 TONBATT : 0 seconds CUMONBATT: 0 seconds XOFFBATT : N/A SELFTEST : NO STATFLAG : 0x07000008 Status Flag SERIALNO : AS0603298896 BATTDATE : 2006-01-14 NOMOUTV : 120 Volts NOMBATTV : 24.0 Volts FIRMWARE : 601.3.D USB FW:1.5 APCMODEL : Smart-UPS 1500 END APC : Thu Mar 29 13:02:12 EDT 2012 

运行最新的错误

 You are using a SMART cable type, so I'm entering SMART test mode mode.type = USB_UPS Setting up the port ... Hello, this is the apcupsd Cable Test program. This part of apctest is for testing Smart UPSes. Please select the function you want to perform. 1) Query the UPS for all known values 2) Perform a Battery Runtime Calibration 3) Abort Battery Calibration 4) Monitor Battery Calibration progress 5) Program EEPROM 6) Enter TTY mode communicating with UPS 7) Quit Select function number: 2 First ensure that we have a good link and that the UPS is functionning normally. Simulating UPSlinkCheck ... YWrote: Y Got: getline failed. Apparently the link is not up. Giving up. 

执行破败testing。 这会告诉你电池的实际运行时间,而不是理论运行时间。 它会将负载切换到电池,并运行,直到剩余运行时间或电池电量达到最小允许值,此时它将切换回主电源并为电池充电。

除非电池立即失效,否则不应有任何停机。

要做到这一点:

  • 停止apcupsd服务
  • 运行apctest
  • selectPerform battery calibration